MUT Series 100~600kVA 3-phase Tower UPS


Category: UPS


Product Details


Power range

100~600kVA

Operation

3P/3P,Online double conversion

Applications

Government,Finance,IT,Education,Transportation,Broadcasting,Medical,Energy,etc.

Characteristics

·3P/3P pure online double transformation products,support 380/400/415V,50/60Hz power grid system,to provide the ideal power supply quality and load protection.

·High performance and efficiency,input PF>0.99,THDi<3%,efficiency>96%.

· Full DSP control,flexible and robust digital control for rectifier,inverter and battery management.

·Wide range of voltage and frequency,adapt to different grid and generator input.

·Intelligent system self-diagnosis scheme, rich fault recording,large capacity of history record storage space.

·Redundancy fan design in power module, increasing the system reliability and tolerance.

·Top/bottom cable entry,flexible for different field installation.

Model

TT100

TT120

TT180

TT200

TT240

TT300

TT400

TT500

TT600

Rate Power

100kVA

120kVA

180kVA

200kVA

240kVA

300kVA

400kVA

500kVA

600kVA

 

 

Main input

Input

3P5W(3P+N+PE)

Rate Voltage

380/400/415VAC(L-L);220/230/240VAC(L-N)

Rate Freg

50/60Hz

Input PF

>0.99

Current distortion

THDi<3%(100%Linear load)

Voltage range

304~478VAC(L-L)full load;304~228VAC (L-L)power derate from 100%to 75%

 

Battery

Rate voltage

±240VDC

Charging capacity

20%*Pout

Charging accuracy

±1%

 

Bypass

Rate yoltage

380/400/415VAC(L-L)220/230/240VAC(L-N)

Voltage range

Range:-40%-+25%,Settable,default-20%~+15%

Overload

125%,long time operation  125%<load<130%,
10mins 30%<load <150%,1min >150%,300ms

110%,long time operation  110%<load<125%,
5 mins 125%<load<150%,1 min >150%,1 second

 

 

 

 

Inverter

 

 

 

 

 

 

System

Rate voltage

380/400/415VAC(L-L);220/230/240VAC(L-N)

Rate Freq

50/60Hz

Output PF

1

Noltage accuracy

±1.0%

oad response

<5%(20%-80%-20%step      load)

Recovery time

<20ms(0%-100%-0%step load)

Output THDu

<1%(linear load),<5%(non-linear load according to IEC 62040-3)

Dverload

110%,1 hour;125%,10 mins;150%,1 min;>150%,200ms

Frequency accuracy

0.1%

Synchronize window

Settable,±0.5Hz-±5Hz,default ±3Hz

Slew rate

Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S

Crest factor

3:1

Phase Accuracy

120°±0.5

Efficiency

Normal Mode≥96%;Battery Mode≥96%

Display

LED+7 inch touch LCD

LED +10 inch touch LCD

Certification-Safety

EC62040-1,IEC60950-1

Certification-EMS

IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge)

P degree

IP20

Configuration

USB,RS232,RS485,Dry contact,Cold start,Air filter

Option

SNMP card,AS400 card,Parallel kit,SPD,LBS

Environment

0-40℃(operation);-25℃~70℃(storage);0-95%(Humidity,non-condensing)

Noise(dB)(1 meter)

72dB    @100%load,69dB    @45%load

Dimension

(W*D*H)mm

600*1000*1600

600*1000*2000

1200*1100*2000

Weight

Cabinet

185

248

250

578

Module

41

Power Module rated capacity

50KW

60KW

50KW

60KW

50KW

62.5KW

60KW

Statement:The products will continue to be innovative and optimized,which may lead to asynchronized updates of the actual product and promotional materials.Therefore,this document is for reference only and does not constitute any offer or commitment.